DESIGN METHOD OF PASSIVE SMOKE INSULATION OF THE EVACUATION ROUTE BY MEANS OF AN ATRIUM SOLAR CHIMNEY : Compatibility of solar-assisted natural ventilation and smoke control in an Atrium building

Minegishi, Yoshikazu, et al. "DESIGN METHOD OF PASSIVE SMOKE INSULATION OF THE EVACUATION ROUTE BY MEANS OF AN ATRIUM SOLAR CHIMNEY : Compatibility of solar-assisted natural ventilation and smoke control in an Atrium building." Journal of Environmental Engineering (Transactions of AIJ) 72.611 (2007): 1-6.
DOI: 10.3130/aije.72.1_1

BibTeX RIS

Summary

Proposes an atrium building with a solar chimney that supplies solar-driven stack ventilation in normal use and keeps the evacuation shaft free of smoke during a fire. Scale-model tests and single-zone and two-layer calculations show that smoke exclusion works if the neutral pressure plane stays within the chimney and the leakage openings between the atrium and the shaft are kept below a certain size.

Description written by Solar Tower. The original abstract is available from the publisher via the link below.