Mohammad H. N. Naraghi; Romain Cellard du Sordet · 10.1115/imece2011-63085 https://doi.org/10.1115/imece2011-63085 · 2011 · Building ventilation · Numerical / CFD
ASME 2011 International Mechanical Engineering Congress and Exposition
Building ventilation
Numerical / CFD
2011
ASME 2011 International Mechanical Engineering Congress and Exposition
conference
no
2011-01-01 12:00:00 00003693
stack effect correlation for rooftop solar chimneys
2011
ASME 2011 International Mechanical Engineering Congress and Exposition
Mohammad H. N. Naraghi; Romain Cellard du Sordet
10.1115/imece2011-63085
Summary
Develops a correlation for the airflow through rooftop solar chimneys based on the gap between absorber and glazing, the absorber and incoming air temperatures, and chimney height. Over usual roof pitches (30°–60°) the tilt barely changes the flow, and pairing the correlation with energy balances of the chimney components predicts flow markedly better than the standard stack effect formula.
Description written by Solar Tower. The original abstract is available from the publisher via the link below.