Yoshiteru Shinada; Ken‐ichi Kimura · 10.3130/aije.74.169 https://doi.org/10.3130/aije.74.169 · 2009 · Building ventilation · Experimental
Journal of Environmental Engineering (Transactions of AIJ)
Building ventilation
Experimental
2009
Journal of Environmental Engineering (Transactions of AIJ)
journal
other
yes
2009-01-01 12:00:00 00003919
field measurement on the basic peformance of the natural ventilation system combined with solar chimney and underground pit
2009
Journal of Environmental Engineering (Transactions of AIJ)
Yoshiteru Shinada; Ken‐ichi Kimura
10.3130/aije.74.169
Summary
Field measurements in a newly built school, taken before it opened, assess a natural ventilation system that pairs solar chimneys with an underground pit supplying fresh air. A multi-point calibration let a single anemometer estimate mean chimney airflow. Exhaust and supply volumes matched closely, building blocks ventilated similarly, and chimney airflow tracked solar radiation in calm weather but outdoor wind when sunshine was weak.
Description written by Solar Tower. The original abstract is available from the publisher via the link below.
Open source
PDF (open access)