← Back to publications

CFD investigation of temperature distribution, air flow pattern and thermal comfort in natural ventilation of building using solar chimney

Dhahri, Maher, and Hana Aouinet. "CFD investigation of temperature distribution, air flow pattern and thermal comfort in natural ventilation of building using solar chimney." World Journal of Engineering 17.1 (2020): 78-86.
DOI: 10.1108/wje-09-2019-0261

BibTeX RIS

Summary

ANSYS CFX simulations of a room ventilated by a 45°-inclined solar chimney examine how incoming air temperature, air speed and solar heating shape indoor airflow, temperature fields and comfort. After checking the model against measurements, the authors find all three factors strongly affect comfort, with supply air near 19 °C moving at about 0.15 m/s yielding the most favourable draft-temperature index under ASHRAE criteria.

Description written by Solar Tower. The original abstract is available from the publisher via the link below.

Open source
Scroll to Top